7. Power Isolation / Delayed Access:

Application : Multiple operation programmable Robot Controlled Machines with Guards.

Operating Sequence

  • 7.1  Power ON, Key A trapped / Guard locked closed, Key B trapped – Machine / Robot in normal operation mode.
  • 7.2  At end of cycle, Switch Power off, Key A free. Insert key A in interactive control Box & Trap Key A.
  • 7.3  Key A trapped in interactive control box
    Key B released after end of cycle or preset time delay.
  • 7.4  Release Key-B Insert in Guard lock & trap.
  • 7.5  Key-B Trapped in Guard Door Lock. Guard open.

RECOMMENDED LOCK TYPES : ILT, ILD / ILH – 100

 

8. Locks for Electrical Distribution System.

Three Sources of supply feeding 3 separate loads

Application: Supplies are not to be paralleled at any time. Each source must be able to supply any two loads, if required

Conditions :
Key AA will operate locks AA or A – only.
Key BB will operate locks BB or-B only,
Key AB will operate A-, -B or AB only,

RECOMMENDED LOCK TYPES : ILA, ILB WITH SUITABLE ACCESSORIES